Roll over image to zoom in
MOTOR CIRCUIT-BREAKER PKM0-16
Product code
3730598
PKM0-16 motor protection circuit breaker.
- Rated current 16 A, adjustment range 10-16 A
- Motor power AC-3 7.5 kW (400 V)
- Thermal trip type
- Electromagnetic trip
- Electromagnetic trip setting 20 x In
- Short-circuit protection 224 A
- Dimensions: width 45 mm, height 93 mm, depth 76 mm
- Motor protection circuit breakers also respond to loss of one phase
- Suitable for IE3 efficiency class motors
- Standards: IEC/EN 60947, VDE 0660, UL, CSA
- Finger and touch protected
Motor protection circuit breakers without overload protection, providing protection only against short circuits. Used in circuits where there is no risk of overload or where overload protection is already in place. Rated currents 0.16-32 A.
This product description is an automated translation of the original Finnish description.Product details
Technical specifications
Product class (ETIM)Motor protection circuit-breaker (EC000074)
Adjustment range undelayed short-circuit release248-248 A
With thermal overload protectionno
Phase failure sensitiveno
Switch off techniqueMagnetic
Rated operating voltage690-690 V
Rated permanent current Iu16 A
Rated operation power at AC-3, 230 V4 kW
Rated operation power at AC-3, 400 V7.5 kW
Power loss6.43 W
Type of electrical connection of main circuitScrew connection
Type of control elementTurn button
Device constructionBuilt-in device fixed built-in technique
With integrated auxiliary switchno
With integrated under voltage releaseno
Number of poles3
Product codes
SAPATB608
STK3730598
PLC3730598
GTIN/EAN4015080445029
Manufacturer part number044502
Vendor material number044502
Basic information
Package measurements (L x W x H)77 x 45 x 93 mm
Package volume0.322 l
Package weight0.293 kg
Base uniteach
Package units1
Package contents–
UNSPSC39121521
BrandEATON
VendorEATON ELECTRIC OY