SURGE ARRESTER ELTAKO MUA-20 T2+T3,3L+N+PE

Product code
3209100
Overvoltage protector MUA-20 reliably protects electrical systems from transient overvoltages. It protects TN and TT systems against switching overvoltages and indirect lightning strikes. Its compact design, simple DIN-rail mounting, and modular construction enable quick installation and maintenance. It provides Type 2 + Type 3 protection and reliably guards against transient overvoltages caused by network switching operations or distant lightning strikes. The use of MUA-20 is recommended, for example, when the cable length between the main/metering distribution board and the sub-distribution/distribution board exceeds 10 meters. If a building has an external lightning protection system, staged overvoltage protection must be implemented: Type 1 in the main/metering distribution board (e.g., MUA-100, MUA-50). Type 2 in sub-distribution/distribution boards (e.g., MUA-30, MUA-20). Type 2 overvoltage protection in a sub-distribution board is required only if the cable length from the main distribution board, which is equipped with Type 1+2+3 overvoltage protection, exceeds 10 meters. TECHNICAL DATA Grounding system TN/TT Rated voltage 230/400V Maximum operating voltage 275V Nominal discharge current 20kA Maximum discharge current 40kA Protection level ≤ 1.2kV Response time ≤ 25ns Overcurrent protective device (max.) 125 A gL/gG Short-circuit withstand capacity at maximum overcurrent 25kA Protection class IP20 Conductor terminals 35mm² 4 modules = width 72 mm Spare module EM/MUA-20 (Serial No. 32 091 05) Guide for selecting overvoltage protectors Main Distribution Board / Metering Distribution Board Does the building have an external lightning protection system (class 3 or 4)? - Select MUA50. Does the building have an overhead line supply or is it located in a rural or sparsely populated area? - Select MUA30 or MUA50. Is the building located in a densely populated urban area? - Select MUA20. Sub-Distribution Board / Distribution Board Is the incoming supply cable to the sub-distribution board longer than 10 m? - Select MUA20. Is the incoming supply cable to the sub-distribution board shorter than 10 m? - Overvoltage protection is not required. This product description is an automated translation of the original Finnish description.

Product details

Technical specifications

Product class (ETIM)Surge protection device for power supply systems (EC000941)
System configuration DCno
System configuration ITno
System configuration TNyes
System configuration TN-Cyes
System configuration TN-C-Syes
System configuration TN-Syes
System configuration TTyes
System configuration otheryes
Number of conductors (without earthing)4
Nominal discharge surge current (8/20)20 kA
Max. discharge surge current (8/20)40 kA
Nominal voltage AC230 V
Max. continuous voltage AC275 V
Voltage protection level1.2 kV
Max. overcurrent protection device, parallel connection (fuse)125 A

Product codes

SAPDLZ818
STK3209100
PLC3209100
GTIN/EAN4010312502198
Manufacturer part numberMUA-20
Vendor material number3209100

Basic information

Package measurements (L x W x H)94 x 72 x 74 mm
Package volume0.501 l
Package weight0.35 kg
Base uniteach
Package units1
Package contents
UNSPSC39121610
BrandELTAKO
VendorELTAKO GMBH