Roll over image to zoom in


Video
RESIDUAL CURRENT DEVICE GW90922B 40A 30MA TYYPPI B
Product code
3202696
ReStart Autotest automates the testing of residual current devices. If the residual current device is not tested regularly, the tripping mechanism may become stuck, which could result in the device failing to operate during a fault. ReStart Autotest automatically performs the required functional test every 28 days.
ReStart Autotest residual current devices significantly save staff working time, while maintenance costs are also reduced.
In some applications, such as solar power systems and electric vehicle charging points, type B residual current devices must be used. ReStart Autotest provides a solution even when the protected object requires a type B residual current device.
The product is compatible with a fork-type current busbar. This product description is an automated translation of the original Finnish description.
Product details
Technical specifications
Product class (ETIM)Residual current circuit breaker (RCCB) with auxiliary device (EC002693)
Number of poles4
Rated voltage400 V
Rated current40 A
Rated fault current0.03 A
Mounting methodDIN rail
Leakage current typeA
Selective protectionno
Short-time delayed trippingyes
Short-circuit breaking capacity (Icw)10 kA
Surge current capacity3 kA
Additional equipment integratedSelftest, automatic reclosing and auxiliary switch
Additional equipment attached at deliveryMonitoring unit with automatic reclosing
Rated switch current auxiliary device40 A
Rated voltage auxiliary device230 V
Control voltage type auxiliary equipmentAC
Product codes
SAPCYL077
STK3202696
PLC3202696
GTIN/EAN8034035040573
Manufacturer part numberGW90922B
Vendor material numberGW90922B
Basic information
Package measurements (L x W x H)155 x 130 x 105 mm
Package volume2.116 l
Package weight0.953 kg
Base uniteach
Package units1 / 2 / 180
Package contents–
UNSPSC39121614
BrandGEWISS
VendorPERFORMANCE IN LIGHTING OY FINLAND
Documents (8)
Brochures & documents