Roll over image to zoom in




Video
ARC FAULT DETECTION DEVICE ARC966D 1P+N C-16A 6KA JL 2M
Product code
3246436
Arc fault protection according to DIN EN 62606 (VDE 0665-10), combined with a 1L+N line protection circuit breaker and electronic residual current detection (300 mA) to enhance fire protection for circuits not protected by residual current devices. The device is equipped with QuickConnect spring terminals according to DIN EN 60898-1 (VDE 0641-11). It features a blue Test button for arc fault indication. Individual devices can be easily added or replaced from the busbar. Can be equipped with retrofittable additional or auxiliary modules. Group labeling possible via the device's labeling window. This product description is an automated translation of the original Finnish description.
Product details
Technical specifications
Product class (ETIM)Miniature circuit breaker (MCB) with auxiliary device (EC002694)
Release characteristicC
Number of poles2
Rated current16 A
Rated voltage230 V
Rated short-circuit breaking capacity according to EN 608986 kA
Rated short-circuit breaking capacity according to IEC 60947-26 kA
Voltage typeAC
Current limiting class3
Frequency50-50 Hz
Concurrently switching neutral conductoryes
Overvoltage category3
Pollution degree2
Width in number of modular spacings2
Built-in depth70 mm
Additional equipment attached at deliveryFire protection switch
Product codes
SAPCVD017
STK3246436
PLC3246436
GTIN/EAN3250611013211
Manufacturer part numberARC966D
Vendor material number3246436
Basic information
Package measurements (L x W x H)75 x 35 x 96 mm
Package volume0.252 l
Package weight0.217 kg
Base uniteach
Package units1 / 60 / 60 / 1440
Package contents–
UNSPSC39121614
BrandHAGER
VendorUTU OY
Documents (11)
Certificates
Brochures & documents
Links
Environment and safety
Carbon footprint data
Carbon footprint of product manufacturing (A1–A3 GWP value)0.1033
GWP, uniteach
Source for GWP dataEPD
Documents (1)