RCCB 2P 16A 10mA A
Residual current device (RCD) in accordance with standards EN 61008-1, DIN EN 61008-2-1, and VDE 0664 part 10 + 11, touch protection IP2x in accordance with DIN VDE 0106 part 100. Suitable also for protection of retrofitted circuits (tool-free mounting). Terminal connections equipped with wire entry protection. Double connector for cable and busbar connection below, separate blue test button for RCD testing. Module equipped with a hinged label pocket for circuit labeling. This product description is an automated translation of the original Finnish description.

Product details

Technical specifications

Product class (ETIM)Residual current circuit breaker (RCCB) (EC000003)
Number of poles2
Rated voltage230 V
Rated current16 A
Rated fault current0.01 A
Rated insulation voltage Ui500 V
Rated impulse withstand voltage Uimp4 kV
Power loss2.4 W
Mounting methodDIN rail
Leakage current typeA
Selective protectionno
Short-time delayed trippingno
Short-circuit breaking capacity (Icw)6 kA
Surge current capacity0.25 kA
Voltage typeAC
With interlocking deviceyes

Product codes

SAPAEE328
STK3260801
PLC3260801
GTIN/EAN3250611610014
Manufacturer part numberCCA216D
Vendor material number3260801

Basic information

Package measurements (L x W x H)40 x 100 x 80 mm
Package volume0.32 l
Package weight0.22 kg
Base uniteach
Package units1 / 60 / 1440
Package contents
UNSPSC39121614
BrandHAGER
VendorUTU OY

Documents (7)

Environment and safety

Carbon footprint data

Carbon footprint of product manufacturing (A1–A3 GWP value)0.2939
GWP, uniteach
Source for GWP dataEPD

Documents (1)

Sustainability brochures & documents

Manufacturer

NameUTU Oy
Postal addressAhjontie 1, 28400 Ulvila