RCD CEA225N 100MA A/2X25A

Product code
3260878
Residual current device (RCD) in accordance with standards EN 61008-1, DIN EN 61008-2-1, and VDE 0664 part 10 + 11, touch protection IP2x in accordance with DIN VDE 0106 part 100. Suitable also for protection of retrofitted circuits (tool-free mounting). Terminal connections equipped with wire entry protection. Double connector for cable and busbar connection below, separate blue test button for RCD testing. Module equipped with a hinged label pocket for circuit labeling. This product description is an automated translation of the original Finnish description.

Product details

Technical specifications

Product class (ETIM)Residual current circuit breaker (RCCB) (EC000003)
Number of poles2
Rated voltage230 V
Rated current25 A
Rated fault current0.1 A
Rated insulation voltage Ui500 V
Rated impulse withstand voltage Uimp4 kV
Mounting methodDIN rail
Leakage current typeA
Selective protectionyes
Short-time delayed trippingno
Short-circuit breaking capacity (Icw)1.5 kA
Surge current capacity3 kA
With interlocking deviceyes
Frequency50 Hz
Additional equipment possibleyes

Product codes

SAPAIU412
STK3260878
PLC3260878
GTIN/EAN3250611616887
Manufacturer part numberCEA225N
Vendor material number3260878

Basic information

Package measurements (L x W x H)40 x 100 x 80 mm
Package volume0.32 l
Package weight0.19 kg
Base uniteach
Package units1 / 60 / 1440
Package contents
UNSPSC39121614
BrandHAGER
VendorUTU OY

Documents (5)

Certificates

Environment and safety

Manufacturer

NameUTU Oy
Postal addressAhjontie 1, 28400 Ulvila