Roll over image to zoom in



INSTALLATION CABLE-FRHF NHXH 7G2,5 FE180/E90 D500
Product code
0409820
Installation/control cable FRHF, (N)HXH 7x2.5 mm2 FE180/PH120/E90 Orange, K500, outer Ø 13.4 mm, HFFR.
The flame-retardant and halogen-free NHXH installation/control cable is designed for fixed electrical installations in dry or humid environments where operational safety during a fire is required. Suitable as an industrial and production control cable. OBO NHXH installation cables have been tested for cable system fire resistance class E90 according to standard DIN 4102-12. The cable is VDE certified and suitable for use at a voltage range of 600/1000 V.
The cable's outer sheath is protected against UV radiation, but if the cable is exposed to sunlight, we recommend protecting it, for example, with a protective conduit or cable tray. The cable may be installed directly into the ground only when using a protective conduit.
E90 cable system testing and VDE E90 certification have been performed with OBO BETTERMANN and BAKS cable trays and mounting accessories.
- 180 min fire resistance (FE 180) IEC 60331-21 / EN 50200
- 120 min fire resistance with shock (PH 120) EN 50200
- Self-extinguishing in bundles IEC 60332-3-24 Cat C
- Low smoke emission IEC 61034-2
- Cable system fire resistance (E90) DIN 4102-12
- VDE Certified
Technical specifications:
• Operating voltage: 600/1000 VAC
• Test voltage: 4000 V
• Conductor resistance: 2.5 mm²: <7.41 ohm/km
• Operating temperature: -20 °C … +70 °C
• Minimum bending radius: 10 x D
• Packaging: Reel 500 m
Construction
• Conductors: Electrolytic solid copper wire, Class 1 IEC 60228 / DIN EN 60228 / EN 60228
• Conductor insulation: Cross-linked halogen-free polymer compound (Silicon) EN-50363-5 EI8
• Conductor colors: 7-core: yellow/green and black conductors numbered 1-6
• Insulation thickness over conductor: 2.5 mm²: 0.60 mm
• Inner insulation material: HFFR
• Outer sheath: HFFR, RAL 2003, orange (EN 50290-2-27)
• Outer sheath diameter: 13.4 mm
- Flame Retardant Test: IEC 60332-1-2
- Flame Propagation Test: IEC 60332-3-24 Cat C
- Smoke Density: IEC 61034-2
- Corrosive Gas Test: IEC 60754-2
- Halogen Free Test: IEC 60754-1
- Circuit Integrity Test: IEC 60331-21 (FE/180)
- Circuit Integrity With Shock Test: EN 50200 (PH/120) This product description is an automated translation of the original Finnish description.
Product details
Technical specifications
Product class (ETIM)Power cable < 1 kV, for permanent installation (EC003248)
Conductor materialCopper
Conductor surfaceBare
Nominal cross section conductor2.5 mm²
Conductor categoryClass 1 = solid
Conductor resistance at 20 °C7.41 Ohm/km
Number of cores7
Twisted coresyes
Material core insulationOther
Specification core insulationOther
Identification/coding colour coreOther
Core identificationNumbers
Core colourBlack
With protective conductoryes
Drain wireno
Lead sheathno
Product codes
SAPDIH403
STK0409820
PLC0409820
GTIN/EAN6430078842785
Manufacturer part numberNHXH 7x2.5 mm2-500
Vendor material number0409820
Basic information
Package measurements (L x W x H)1000 x 13 x 13 mm
Package volume0.169 l
Package weight0.387 kg
Base unitMeter
Package units500 / 1000
Package contents–
UNSPSC26121613
BrandLAATUANTENNI
VendorLAATUANTENNI OY
Documents (5)
Certificates
Brochures & documents
Links