Roll over image to zoom in



LIGHTNING CONTROLLER MC50-B/O
Product code
5808001
LightningController plug-in arrester
MC 50-B 0 VDE Protection Module
Type 1 surge protectors conduct the discharge current of a direct lightning strike to ground via the grounding electrode and limit the resulting overvoltages to a safe level.
According to SPD standard EN 61643-11 Type 1
According to SPD standard IEC 61643-11 Class I
Installation method base unit
Model 1-pole
Protection class IP 20
Discharge capacity (8/20) [total] (kA) 50
Ignition time (ns) <100
Follow current interruption capacity lpeak (kA) 25
Follow current interruption capacity leff (kA) 12.5
Maximum continuous voltage (V) 255
Lightning current (10/350) (kA) 50
Short-circuit withstand (kA) 25
Nominal discharge current (8/20) (kA) 50
Nominal voltage (V) 230
Maximum fuse rating (A) 500
Protection level (kV) <2.0
No marking on device
Distribution unit TE (17.5 mm) 2
Temperature range (°C) -40 : +85
When a direct lightning strike hits a building protected by an external lightning protection system, large potential differences can arise between the building and installed systems (electrical, telecommunications cables), leading to dangerous fires and damage. Nearby lightning strikes generate strong magnetic fields that can damage electrical equipment. But even lightning strikes up to 2 km away can generate dangerous overvoltages in the building's electrical equipment. OBO provides all necessary products for reliable lightning protection: surge protectors, overvoltage protectors, potential equalization and grounding accessories. This product description is an automated translation of the original Finnish description.
Product details
Technical specifications
Product class (ETIM)Lightning current arrester for power supply systems (EC000381)
System configuration ITno
System configuration TNyes
System configuration TN-Cyes
System configuration TN-C-Syes
System configuration TN-Syes
System configuration TTyes
Lightning impulse current (10/350 µs)50 kA
Nominal discharge surge current (8/20)50 kA
Max. continuous voltage AC255 V
Nominal voltage AC230 V
Voltage protection level2 kV
Follow current extinguishing capability25 kA
Mounting methodOn basic element
Construction size2 modular spacing
With remote signalling contactno
Product codes
SAPABM991
STK5808001
PLC5808001
GTIN/EAN4012195480730
Manufacturer part number5096820
Vendor material number5096820
Basic information
Package measurements (L x W x H)100 x 100 x 50 mm
Package volume0.5 l
Package weight0.1 kg
Base uniteach
Package units1
Package contents–
UNSPSC39121621
BrandOBO BETTERMANN
VendorOBO BETTERMANN OY
The country of origin stated by the supplierFinland