CIRCUIT BREAKER IC60N 1X40A/C/6KA

Product code
3262240
IC60N, miniature circuit breaker, 1p, 40A, C curve
IC60N, miniature circuit breaker, 1p, 40A, C curve. device application: distribution - range: Acti 9 - product or component type: miniature circuit-breaker - product name: iC60 - device short name: iC60N - network type: AC, DC - trip unit technology: thermal-magnetic - breaking capacity: 10 kA Icu conforming to EN 60947-2 - 220...240 V AC 50/60 Hz, 10 kA Icu conforming to EN 60947-2 - 72 V DC, 10 kA Icu conforming to IEC 60947-2 - 220...240 V AC 50/60 Hz, 10 kA Icu conforming to IEC 60947-2 - 72 V DC, 15 kA Icu conforming to EN 60947-2 - 12...60 V DC, 15 kA Icu conforming to IEC 60947-2 - 12...60 V DC, 20 kA Icu conforming to EN 60947-2 - 100...133 V AC 50/60 Hz, 20 kA Icu conforming to IEC 60947-2 - 100...133 V AC 50/60 Hz, 36 kA Icu conforming to EN 60947-2 - 12...60 V AC 50/60 Hz, 36 kA Icu conforming to IEC 60947-2 - 12...60 V AC 50/60 Hz, 6000 A Icn conforming to EN 60898-1 - 230 V AC 50/60 Hz, 6000 A Icn conforming to IEC 60898-1 - 230 V AC 50/60 Hz - utilisation category: category A conforming to EN 60898-1, category A conforming to IEC 60898-1 - suitability for isolation: yes conforming to EN 60898-1, yes conforming to EN 60947-2, yes conforming to IEC 60898-1, yes conforming to IEC 60947-2 - standards: EN 60898-1, EN 60947-2, IEC 60898-1, IEC 60947-2. Benefits: - The new reference in final distribution,, Absolute safety of circuit protection with VisiSafe,, Greater continuity of service with VisiTrip,, Simple to choose with meaningful part numbers,, Easy to install with quick, ergonomic & safe IP20B terminal shutters & robust connections (twice the standard tightening torque),, Environmentally friendly with 100% recyclable & recoverable materials.... Applications: Low-voltage final distribution, Protection of electrical circuits in all industrial and commercial buildings,, All applications, especially in polluted environments and networks,, Motor circuit protection,, DC current circuit protection....

Product details

Technical specifications

Built-in depth44.5 mm
Release characteristicC
Number of poles (total)1
Number of protected poles1
Rated current40 A
Rated voltage230 V
Rated insulation voltage Ui500 V
Rated impulse withstand voltage Uimp6 kV
Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V6 kA
Voltage typeAC/DC
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V10 kA
Frequency50 ... 60 Hz
Current limiting class3
Concurrently switching neutral conductorfalse
Over voltage category4

Product codes

SAPCAL094
PLC3262240
STK3262240
GTIN/EAN3606480440403
Manufacturer part numberA9F04140
Vendor material number3262240

Basic information

Package measurements (L x W x H)18 x 92 x 78 mm
Package volume0.129 l
Package weight0.125 kg
Base uniteach
Package units1 / 12
Package contents
UNSPSC39121603
BrandSCHNEIDER ELECTRIC
VendorSCHNEIDER ELECTRIC FINLAND OY

Documents (4)