CONTROL RELAY CURRENT AR12DX-230V

Product code
2701804

DIN-rail current monitoring relay, 0.1-32A.

Operation

Using the internal toroidal transformer, the alternating current flowing through the device's V1 (terminals M1-M2) is compared to the relay's set value, adjustable via rotary switches A (base current) and xA (multiplier) on a scale of 0.1–32A. If the set value is exceeded, the relay switches off device V2 (connected to terminal 2) or switches to device V3 (connected to terminal 3) within 0.5 seconds. When the set value falls below the threshold again, the contact switches back after the release delay set by the RV rotary switch; the release delay is adjustable between 0–120 seconds.

Rotary switches

The base current A is set using the lowest rotary switch A. Possible base values are 0.1A; 0.3A; 0.6A; 0.9A; 1.5A; 1.9A; 3.0A; and 3.2A. The multiplier xA is set using the middle rotary switch xA; available values range from 1 to 10. Thus, currents can be set starting from 0.1A (base current set to 0.1A and multiplier set to 1). The release delay RV can be set between 0–120 seconds using the uppermost RV rotary switch. A red LED indicator below the rotary switch flashes during the set RV time.

  • 1 potential-free changeover contact (CO) 16A/250V AC.
  • Standby power consumption only 0.8 watts.
  • LED load up to 200W.
  • Incandescent lamp load up to 2300W.
  • 1 module = width 18mm, depth 58mm.
  • Using the patented Eltako Duplex technology (DX), normally potential-free contacts can still be connected at the 230V AC 50Hz neutral point, significantly reducing their wear.
  • Modern hybrid technology combining the advantages of wear-free electronic control with those of high-performance special relays.
  • Setting accuracy ± 5%.
  • From 25A onwards, the relay always switches on.
This product description is an automated translation of the original Finnish description.

Product details

Technical specifications

Product class (ETIM)Current monitoring relay (EC001440)
Type of electric connectionScrew connection
With detachable clampsno
Current measuring range0.1-32 A
Single-phase under current possibleno
Three-phase under current possibleno
Single-phase overcurrent possibleno
Three-phase overcurrent possibleno
Single-phase hysteresis possibleno
Three-phase hysteresis possibleno
Contains function DC-voltage under currentno
Contains function DC-voltage overcurrentno
Function DC-current hysteresisno
Min. adjustable off-delay time0 s
Max. permitted off-delay time120 s
External current transformerno

Product codes

SAPCBC239
STK2701804
PLC2701804
GTIN/EAN4010312205426
Manufacturer part numberAR12DX-230V
Vendor material number2701804

Basic information

Package measurements (L x W x H)90 x 23 x 65 mm
Package volume0.135 l
Package weight0.08 kg
Base uniteach
Package units1 / 10 / 100 / 20000
Package contents
UNSPSC39122325
BrandELTAKO
VendorELTAKO GMBH