Roll over image to zoom in



CONTROL RELAY CURRENT SBR61-230V/120µF
For mounting in a control box. Length 45 mm, width 45 mm, depth 18 mm.
Max. capacitive load of 120?F after rectifier (e.g. energy-saving lamp or HF ballast) or 6 ?F directly from the mains (e.g. parallel-compensated fluorescent lamp). Limiting resistor of 24?, which limits the inrush current to 15 milliseconds. The switching current for energy-saving lamps, fluorescent lamps, and small fluorescent lamps is limited to 10 A due to the effect of the power resistor (24?) through a short switching-on time (approx. 15 milliseconds). The current-limiting relay is connected between the contact of the controlled relay and the load. Continuous load up to 600 W, maximum switching frequency 600/h.
Explanation of capacitive load:The specified maximum capacitive load directly from the mains is the determining factor for example for parallel-compensated fluorescent lamps and conventional loads. If a capacitor is connected in parallel to the electrical supply, the determining factor defines the correct lamp-specific sizing. The specified maximum capacitive load after the rectifier is the determining factor for energy-saving lamps and HF ballasts. A capacitance of 10?F per lamp is calculable.
This product description is an automated translation of the original Finnish description.