
Roll over image to zoom in




CABLE CABINET E-MOBILITY AHMA LKM25236X
- Rated current 250A (available in 160A / 200A / 250A)
- Outputs: 36 units of MCN320E (Hager cable protection breaker C-curve 20A, 3-pole)
- Input: Compact breaker HNJ250DR with mounting rail (Hager H3+)
- Network analyzer with ModBus communication interface (Circutor CVM-C11)
- Input connectors HYW007H (Al/Cu 2x35-300mm˛)
- Charging output connectors: Al/Cu terminal connectors 2.5-35mm˛
In electric vehicle charging, the output components of the station often operate near their rated current, making temperature management critically important for the station’s lifespan.
The station incorporates temperature management requirements suited to charging load:- Field-specific ventilation
- Air gaps in charging outputs
- Thermal emergency shutdown function
Charging output balancing factor is 1 (as required by the charging station standard).
The station features DIN rail mounting for sensors, enabling readiness for dynamic temperature management. When connected to an eParking backend system, the charging station can dynamically control charging load based on the temperature of output components.
Lifecycle ManagementThe station includes reserved space for load management devices. The load management space is a general device compartment suitable for installing any devices. Reserved space is provided for the eTolppa system’s load management device (eG) to support multi-level load management. When the eTolppa load management device is installed in the station, no separate connection device is required at charging points.
If the thermal emergency shutdown function repeatedly interrupts power supply during the station’s lifecycle, it is advisable to implement dynamic temperature management. In this mode, the backend system can continuously limit charging station loads based on the temperature of output components.
The station includes reserved space for a harmonic filter. The network analyzer can monitor the development of harmonic distortions, and a harmonic filter can be easily added later. Alarms related to harmonics can be added to the analyzer.
The station also includes a separate compartment for spare outputs. The spare output compartment comes standard with 3 units of C10 and 2 units of C16 (1-pole) circuit breakers (for other electrical needs). Spare outputs are not wired to busbars.
This product description is an automated translation of the original Finnish description.