CABLE CABINET E-MOBILITY AHMA LK12116X
- Rated current 125A (available in 80A / 100A / 125A)
- Outputs: 16x MCN316E (Hager circuit breaker, C-curve, 16A, 3-pole)
- Input: Compact circuit breaker HHS125DC with mounting rail (Hager H3+)
- Network analyzer with ModBus communication interface (Circutor CVM-C11)
- Input connectors HYS005H (Al/Cu 35-120mm²)
- Charging output connectors: Al/Cu terminal blocks 2.5-35mm²
In electric vehicle charging, the output components of the station often operate near their rated current, making temperature management critical for the station’s service life.
The station incorporates temperature management features tailored to charging load demands:- Field-specific ventilation
- Air gaps at charging outputs
- Thermal emergency shutdown function
Charging output balancing factor of 1 (as required by the charging station standard).
The station includes DIN-rail mounting for sensors, enabling readiness for dynamic temperature management. When connected to an eParking backend system, the charging station can dynamically control charging load based on the temperature of output components.
Service Life ManagementThe station includes a dedicated device compartment for load management devices. This device compartment is a general-purpose space suitable for installing any device. It has reserved space for the eTolppa system’s load management device (eG) to support multi-level load management. When the eTolppa load management device is installed in the station, no separate connection device is required at charging points.
If the thermal emergency shutdown function repeatedly interrupts power supply during the station’s service life, it is advisable to implement dynamic temperature management. In this mode, the backend system can continuously limit charging station loads based on the temperature of output components.
The station includes reserved space for a harmonic filter. The network analyzer can monitor the development of harmonic distortions, and a harmonic filter can be easily added later. Alarms related to harmonics can also be configured on the analyzer.
The station also includes a separate compartment for spare outputs. The spare output compartment is standardly equipped with 3x C10 and 2x C16 (1-pole) circuit breakers (for additional electrical needs). Spare outputs are not wired to busbars.