CABLE CABINET E-MOBILITY AHMA LK25148VX
- Rated current 250A (available in 160A / 200A / 250A)
- Outputs: 48 units of ADM466C (Hager residual current device, C-curve 16A, 4-pole 30mA)
- Supply: Compact circuit breaker HNJ250DR with busbar mounting (Hager H3+)
- Network analyzer with ModBus communication interface (Circutor CVM-C11)
- Supply connectors HYW007H (Al/Cu 2x35-300mm˛)
- Charging outputs: Al/Cu terminal connectors 2.5-35mm˛
In electric vehicle charging, the output components of the station often operate near their rated current, making temperature management critically important for the station’s service life.
The station incorporates temperature management requirements according to charging load:- Field-specific ventilation
- Air gaps in charging outputs
- Thermal emergency shutdown function
Charging output balancing factor 1 (as required by the charging station standard).
The station features DIN rail mounting for sensors, enabling readiness for dynamic temperature management. When connected to the eParking backend system, the charging station can dynamically control charging load based on the temperature of output components.
Service Life ManagementThe station includes reserved space for load management devices. Load management space is a general device compartment suitable for installing any device. The compartment has reserved space for the eTolppa system load management device (eG) to enable multi-level load management. When the eTolppa system load management device is installed in the station, no separate connection device is required at charging stations.
If the thermal emergency shutdown function repeatedly interrupts power supply during the station’s service life, it is advisable to implement dynamic temperature management. In this mode, the backend system can continuously limit charging station loads based on the temperature of output components.
The station includes reserved space for a harmonic filter. The network analyzer can monitor the development of harmonic distortions, and a harmonic filter can be easily added to the station afterward. Alarms related to this can be added to the analyzer.
The station also has a separate compartment for spare outputs. The spare output compartment includes as standard 3 units of C10 and 2 units of C16 (1-pole) circuit breakers (for other electrical needs). Spare outputs are not wired to busbars.
This product description is an automated translation of the original Finnish description.