CABLE CABINET E-MOBILITY AHMA LKM16132VX
- Rated current 160A (selectable 100A / 125A / 160A)
- Outputs: 32 units of ADM466C (Hager residual current device, C-curve 16A, 4-pole, 30mA)
- Input: Compact breaker HHT160DR with mounting rail (Hager H3+)
- Network analyzer with ModBus communication (Circutor CVM-C11)
- Input connectors HYT005H (Al/Cu 50-185mm²)
- Charging output connectors: Al/Cu terminal connectors 2.5-35mm²
In electric vehicle charging, the output components of the station often operate near their rated current, making temperature management critical for the station’s lifespan.
The station incorporates temperature management requirements suited to charging load:- Field-specific ventilation
- Air gaps in charging outputs
- Thermal emergency shutdown function
Output balancing factor is 1 (as required by the charging station standard).
The station features DIN rail mounting for sensors, enabling readiness for dynamic temperature management. When connected to an eParking backend system, the charging station can dynamically control charging load based on the temperature of output components.
Lifecycle ManagementThe station includes reserved space for load management devices. The device space is a general-purpose area suitable for installing any device. Reserved space is provided for the eTolppa system’s load management device (eG) for multi-level load management. When the eTolppa load management device is installed in the station, no separate connection device is required at charging stations.
If the thermal emergency shutdown function repeatedly interrupts power supply during the station’s lifecycle, it is advisable to implement dynamic temperature management. In this mode, the backend system can continuously limit charging station loads based on the temperature of output components.
The station includes reserved space for a harmonic filter. The network analyzer can monitor the development of harmonic distortions, and a harmonic filter can be easily added later. Alarms related to harmonics can be added to the analyzer.
The station also includes a separate space for spare outputs. The spare output space comes standard with 3 units of C10 and 2 units of C16 (1-pole) circuit breakers (for other electrical needs). Spare outputs are not wired to busbars.